EasyManuals Logo
Home>Midea>Air Conditioner>VRF Series

Midea VRF Series User Manual

Midea VRF Series
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #125 background imageLoading...
Page #125 background image
V6R VRF 50/60Hz
124
Midea
V6R
Series Service Manual
2.19 P1: High pressure protection
Digital display output
Description
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
High pressure sensor protection
Trigger condition: Discharge pressure ≥ 3.9 MPa.
Recover condition:
Cooling Only/Main Cooling Discharge pressure < 3.5MPa and Restart permission=ON.
Heating Only/Main Heating Discharge pressure < 3.1MPa and Restart permission=ON.
Reset method: Resume automatically.
Discharge pressure switch protection
Trigger condition: Discharge pressure 4.0 MPa.
Recover condition: Discharge pressure < 3.0MPa.
Possible causes
Outdoor unit stop valves are closed.
Pressure sensor/switch not connected properly or has malfunction.
Excess refrigerant.
System contains air or nitrogen.
High pressure side blockage.
Poor condenser heat exchange.
Outdoor main PCB damaged.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea VRF Series and is the answer not in the manual?

Midea VRF Series Specifications

General IconGeneral
BrandMidea
ModelVRF Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals