V6R VRF 50/60Hz
92
Midea
V6R
Series Service Manual
2.5 E5: Abnormal power supply voltage
Digital display output
Description
Abnormal power supply voltage.
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Outdoor unit power supply phase voltage < 170V or ≥ 270V.
Recover condition: Outdoor unit power supply phase voltage is 180V and < 260V.
Reset method: Resume automatically.
Possible causes
Outdoor unit power supply voltage is abnormal or a phase is missing.
Loosened wiring within electric control box.
High voltage circuit error.
Outdoor main PCB damaged.