V6R VRF 50/60Hz
36
Midea V
6R Series Service Manual
5.6 Outdoor Fan Control
The speed of the outdoor unit fans is adjusted in steps, as shown in Table 3-5.9
Table 3-5.9: Outdoor fan speed steps
Fan speed index
Fan speed (rpm)
Note
8-12HP
14-20HP
FANA / FANB
0
0
0/0
Stop operation
Startup or defrosting control
1
120
150/0
2
130
180/0
3
140
210/0
4
150
240/0
5
170
270/0(150/150)
6
190
300/0(180/180)
7
210
330/0(210/210)
8
230
360/0(240/240)
9
250
270/270
10
280
300/300
11
310
330/330
12
340
360/360
13
370
390/390
14
400
420/420
15
430
460/460
16
460
500/500
17
500
540/540
18
530
580/580
19
560
620/620
20
600
660/660
21
630
710/710
22
660
760/760
23
700
810/810
24
740
860/860
8/14HP Standard step
25
780
910/910
10/16HP Standard step
26
820
960/960
12/18/20HP Standard step
27
860
1000/1000
28
900
1040/1040
29
940
1080/1080
30
980
1120/1120
Notes:
1. Standard step means the max. step in standard static pressure mode (0Pa default).
Table 3-5.10 Upper limit fan step in static pressure mode
Static Pressure mode
Upper limit fan step
(8-12HP)
Upper limit fan step
(14-20HP)
Supper high static pressure mode(80Pa)
+4 step
+4 step
High static pressure mode(60Pa)
+3 step
+3 step
Medium static pressure mode(40Pa)
+2 step
+2 step
Low static pressure mode(20Pa)
+1 step
+1 step
Standard static pressure mode (0Pa. default)
+0 step
+0 step