2 Mode Selection Box Field Settings
2.1 MS01 Switches Settings
Figure 4-2.1: MS01 PCB switches
Table 4-2.1: MS01 PCB switch settings
Refrigerant
leakage
function setting
Refrigerant leakage function invalid (default)
MS01 connected to refrigerant leakage sensor
Dry contact is always closed, and opened when being triggered by refrigerant
leakage (default)
Dry contact is always opened, and closed when being triggered by refrigerant
leakage
Low
temperature
cooling
function
Low temperature cooling function valid (default)
Low temperature cooling function invalid
Refrigerant
leakage sensors
number
Number of refrigerant leakage sensors
S2 S1 ENC1 SW1 SW2 SW3 SW4