Midea V
6R Series Service Manual
8 Other Control
8.1 Overload control
Overload control is used to maintain comfort requirement (i.e. outlet air temperature) and keep proper system pressure.
Figure 3-8.1: Overload control
Notes:
1. Indoor unit operation ratio = Indoor unit operates capacity index (in the same mode)/ outdoor unit capacity index
8.2 Pump-down Control
Recover refrigerant to outdoor unit
Recover refrigerant to outdoor unit is used to recover the refrigerant from indoor units and MS box before service work. The
LED display r001 in this control.
Table 3-8.1: Recover refrigerant to outdoor unit
Tes = -15°C
Upper limit: 60 Hz
Electronic
expansion valve
Refer to
startup control
in cooling
operation
Cooling only normal control
Electronic
expansion valve
Electronic
expansion valve
Electronic
expansion valve
Meet any points below:
• Pump down time elapses 5min.
• Pe < 0.12MPa
• T7C1_Max ≥ 105°C
• Pc ≥ 3.6MPa
Notes:
1. Pc: Discharge pressure Pe: Suction pressure
2. Tes : Target evapating temperature T7C1: Compressor discharge temperature
Indoor unit operation ratio ≥ 130%
Indoor unit operation ratio <105%
Overload control, indoor units operates in
low fan speed