Part 5
-
Electrical Components and Wiring Diagrams
Table 5-2.3: Menu mode function (continued)
Low locking capacity (Tcs0=42)
Only available for master unit (Tc target temperature during heating operation, Automatic
control)
Medium-to-low locking capacity
(Tcs0=44)
Only available for master unit (Tc target temperature during heating operation, Locking)
Medium locking capacity (Tcs0=46)
Only available for master unit (Tc target temperature during heating operation, Locking)
Medium-to-high locking capacity
(Tcs0=48)
Only available for master unit (Tc target temperature during heating operation, Locking)
High locking capacity (Tcs0=51)
Only available for master unit (Tc target temperature during heating operation, Locking)
Fahrenheit degree setting (
o
F)
Only available for the master unit
Celsius degree setting (
o
C)
Only available for the master unit
According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for
15 minutes and run for 2 minute
According to outdoor ambient temperature (T4), the outdoor fan(s) periodically stop for
30 minutes and run for 2 minute
Exit auto snow-blowing mode
The digital display will display “IdXX”, “XX” stands for VIP address, use UP / DOWN button
to change the VIP address and press OK button to confirm the specified VIP address.
Reverse rotation for dust-clean.
When this function is activated, “ddOn” is displayed. When this function is disabled,
“ddOF” is displayed.
nC2=0 : Remote shut down setting #1: System stops when the circuit (R-OFF1) is
'short'(default)
nC2=1:Remote shut down setting #2:System stops when the circuit (R-OFF1) is 'open'
Start address for automatic addressing
Only available for the master unit
Auto addressing indoor units
Only available for the master unit
Display the online IDU address
Only available for the master unit
Clear IDU address and MS address
Only available for the master unit
Refrigerant leakage protection function 1
Only available for the master unit
Refrigerant leakage protection function 2
Only available for the master unit
Refrigerant leakage protection function 3
Only available for the master unit
Te: Low pressure equivalent saturation temperature (°C) Tes: Target Te value.
Tc: High pressure equivalent saturation temperature (°C) Tcs: Target Tc value.
How to exit specified menu mode:
Table 5-2.4: Exit specified menu mode method:
Long press SW6 “OK” button when the digital
display is not in menu selection state
After running 120 minutes
After running 180 minutes
Long press SW6 “OK” button when the digital
display is not in menu selection state
Select power limitation mode 1 “n41”
Auto snow-blowing mode 1 (2)
UP / DOWN system check button
Before pressing UP or DOWN button, allow the system to operate steadily for more than an hour. On pressing UP or DOWN
button, the parameters listed in Table 5-2.5 will be displayed in sequence.