EasyManuals Logo
Home>Midea>Air Conditioner>VRF Series

Midea VRF Series User Manual

Midea VRF Series
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #97 background imageLoading...
Page #97 background image
V6R VRF 50/60Hz
96
Midea
V6R
Series Service Manual
2.8 E9: EEPROM mismatch of compressor
Digital display output
Description
EEPROM mismatch of compressor.
All units stop running.
Error code is displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Compressor drive parameter is mismatch.
Recover condition: Compressor drive parameter is match.
Reset method: Manually restart.
Possible causes
Outdoor unit was powered on immediately after being powered off.
Outdoor main PCB damaged.
Procedure
E9
The outdoor unit was powered on
immediately after being powered off
1
Yes
Power off the unit and wait for the digital
display to turn off before restarting the
unit
No
Replace the outdoor main PCB
Notes:
1. When performing a manual restart of an outdoor unit, once the unit has been powered off it should not be powered on again until the digital display has
turned off.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea VRF Series and is the answer not in the manual?

Midea VRF Series Specifications

General IconGeneral
BrandMidea
ModelVRF Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals