ADVANCED
advanced 2.9
periodic increase
hot water recirc.
Menu advanced has orange text and is
intended for the advanced user. This menu
has several sub-menus.
Menu
2.9
PERIODIC INCREASE
periodic increase 2.9.1
activated
period
start time
Next periodic increase
days
period
Setting range: 1 - 90 days
Default value: 14 days
start time
Setting range: 00:00 - 23:00
Default value: 00:00
Menu
2.9.1
To prevent bacterial growth in the water heater, the heat pump and the immersion
heater can increase the hot water temperature for a short time at regular intervals.
The length of time between increases can be selected here. The time can be
set between 1 and 90 days. Factory setting is 14 days. Tick/untick "activated" to
start/switch off the function.
HOT WATER RECIRC.
hot water recirc.2.9.2
operating time
downtime min
min
period1
period2
period3
operating time
Setting range: 1 - 60 min
Default value: 60 min
downtime
Setting range: 0 - 60 min
Default value: 0 min
Menu
2.9.2
49Chapter 3 | VVM 320 ā at your serviceNIBE VVM 320