AUTO MODE SETTING
start cooling
stop heating
stop additional heat
filtering time
°C
°C
°C
hrs
auto mode setting4.9.2
start cooling (accessory
required)
Setting range: -20 40 °C
Factory setting: 25
stop heating
Setting range: -20 40 °C
Default values: 17
stop additional heat
Setting range: -25 40 °C
Factory setting: 5
filtering time
Setting range: 0 48 h
Default value: 24 h
Menu
4.9.2
When the operating mode is set to "auto", the indoor module selects when start
and stop of additional heat and heat production is permitted, dependent on the
average outdoor temperature. If accessories for cooling are present or if the heat
pump has the integrated cooling function and it is activated in the menu you can
also select the start temperature for cooling.
Select the average outdoor temperatures in this menu.
Caution
It cannot be set "stop additional heat" higher than "stop heating".
filtering time: You can also set the time (filtering time) over which the average
temperature is calculated. If you select 0, the current outdoor temperature is
used.
NIBE VVM 320Chapter 3 | VVM 320 at your service72

Table of Contents

Other manuals for Nibe VVM 320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe VVM 320 and is the answer not in the manual?

Nibe VVM 320 Specifications

General IconGeneral
BrandNibe
ModelVVM 320
CategoryControl Unit
LanguageEnglish

Related product manuals