1. Basic Understanding of Instructions
10
CS/CJ/NSJ Series Instructions Reference Manual (W474)
Differentiated Instructions
• A differentiated instruction has an internal flag that tells whether the previ-
ous value is ON or OFF. At the start of operation, the previous value flags
for upwardly differentiated instruction (DIFU and @ instructions) are set to
ON and the previous value flags for downwardly differentiated instructions
(DIFD and % instructions) are set to OFF. This prevents differentiation
outputs from being output unexpectedly at the start of operation.
• An upwardly differentiated instruction (DIFU or @ instruction) will output
ON only when the execution condition is ON and flag for the previous
value is OFF.
â–  Using Differentiated Instructions in Interlocks (IL - ILC Instructions)
In the following example, the previous value flag for the differentiated instruc-
tion maintains the previous interlocked value and will not output a differenti-
ated output at point A because the value will not be updated while the
interlock is in effect.
â–  Using Differentiated Instructions in Jumps (JMP(004) - JME(005)
Instructions)
Just as for interlocks, the previous value flag for a differentiated instruction is
not changed when the instruction is jumped, i.e., the previous value is main-
tained.
• With downwardly differentiated instructions (DIFD(014) or instructions
with a %), outputs will turn ON when inputs turn OFF only when the previ-
ous value flag is ON.
• With both upwardly and downwardly differentiated instructions, outputs
will turn OFF in the next cycle.
Note Do not use the Always P_On Flag or A200.11 (First Cycle Flag) as the input
bit for an upwardly differentiated instruction. Do not use the Always P_Off Flag
as the input bit for a downwardly differentiated instruction. If either is used, the
instruction will never be executed.
IL
ILC
DIFU
001000
0.00
0.01
000000
000001
001000
IL is
executing
IL is
executing

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ - INSTRUCTIONS and is the answer not in the manual?

Omron CJ - INSTRUCTIONS Specifications

General IconGeneral
BrandOmron
ModelCJ - INSTRUCTIONS
CategoryController
LanguageEnglish

Related product manuals