Page #340 background image
3. Instructions
302
CS/CJ/NSJ Series Instructions Reference Manual (W474)
COLL
Applicable Program Areas
Operands
Bs: Source Base Address
Of: Offset
The offset can be any value from 0000 to FFFF (0 to 65,535 decimal).
Note Bs and Bs+Of must be in the same data area.
z Operand Specifications
Flags
Instruction Mnemonic Variations
Function
code
Function
DATA COLLECT COLL @COLL 081
Transfers the source word (calculated by adding
an offset value to the base address) to the desti-
nation word.
Symbol
COLL
Area
Function block
definitions
Block program areas Step program areas Subroutines Interrupt tasks
SFC action or
transition programs
Usage OK OK OK OK OK OK
Operand Description Data type Size
Bs Source base address WORD 1
Of Offset WORD 1
D Destination word WORD 1
Area
Word addresses
Indirect DM/EM
addresses
Con-
stants
Registers Flags
Pulse
bits
TR
bits
CIO WR HR AR T C DM EM
@DM
@EM
*DM
*EM
DR IR
Indirect
using IR
TK CF
Bs
OK OK OK OK OK OK OK OK OK OK
--- ---
--- OK --- --- --- ---Of OK
OK
D ---
Name Label Operation
Error Flag ER OFF
Equals Flag = • ON if the source data is 0000.
• OFF in all other cases.
Negative Flag N • ON if the leftmost bit of the source data is 1.
• OFF in all other cases
COLL(081)
Bs
Of
D
Bs: Source base address
Of: Offset
D: Destination word
15 0
Bs
Bs+Of

Table of Contents