3. Instructions
532
CS/CJ/NSJ Series Instructions Reference Manual (W474)
SIND/COSD/TAND
Applicable Program Areas
Operands
îš„ Operand Specifications
Flags
Instruction Mnemonic Variations
Function
code
Function
DOUBLE SINE SIND @SIND 851
Calculates the sine of a double-precision (64-bit)
floating-point number (in radians) and places the
result in the specified destination words.
DOUBLE COSINE COSD @COSD 852
Calculates the cosine of a double-precision (64-
bit) floating-point number (in radians) and places
the result in the specified destination words.
DOUBLE TANGENT TAND @TAND 853
Calculates the tangent of a double-precision (64-
bit) floating-point number (in radians) and places
the result in the specified destination words.
Symbol
SIND COSD TAND
Area
Function block
definitions
Block program areas Step program areas Subroutines Interrupt tasks
SFC action or
transition programs
Usage OK OK OK OK OK OK
Operand Description Data type Size
S First source word LREAL 4
D First destination word LREAL 4
Area
Word addresses
Indirect DM/EM
addresses
Con-
stants
Registers Flags
Pulse
bits
TR
bits
CIO WR HR AR T C DM EM
@DM
@EM
*DM
*EM
DR IR
Indirect
using IR
TK CF
S
OK OK OK OK OK OK OK OK OK OK --- --- --- OK --- --- --- ---
D
Name Label Operation
Error Flag P_ER • ON if the source data is not recognized as floating-point data.
• ON if the source data is not a number (NaN).
• ON if the absolute value of the source data exceeds 65,535.
• OFF in all other cases.
Equals Flag P_EQ • ON if both the exponent and mantissa of the result are 0.
• OFF in all other cases.
Overflow Flag P_OF • SIND, COSD
Unchanged
•TAND
•ON if the absolute value of the result is too large to be expressed as a double-precision (64-bit) float-
ing-point value.
•OFF in all other cases.
Underflow Flag P_UF Unchanged
Negative Flag P_N • ON if the result is negative.
• OFF in all other cases.
S: First source word
SIND(851)
S
D
D: First destination
word
COSD(852)
S
D
S: First source word
D: First destination
word
TAND(853)
S
D
S: First source word
D: First destination
word

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ - INSTRUCTIONS and is the answer not in the manual?

Omron CJ - INSTRUCTIONS Specifications

General IconGeneral
BrandOmron
ModelCJ - INSTRUCTIONS
CategoryController
LanguageEnglish

Related product manuals