3. Instructions
680
CS/CJ/NSJ Series Instructions Reference Manual (W474)
SCL3
Applicable Program Areas
Operands
P1: First Parameter Word
Instruction Mnemonic Variations
Function
code
Function
SCALING 3 SCL3 @SCL3 487
Converts signed BCD data into signed binary data
according to the specified linear function. An offset
can be input in defining the linear function.
Symbol
SCL3
Area
Function block
definitions
Block program areas Step program areas Subroutines Interrupt tasks
SFC action or
transition programs
Usage OK OK OK OK OK OK
Operand Description Data type Size
S Source word WORD 1
P1 First parameter word WORD 5
R Result word INT 1
Note P1 to P1+4 must be in the same area.
S: Source word
P1: First parameter word
R: Result word
SCL3(487)
S
P1
R
∆Y
∆X
P1
P1+1
P1+2
P1+3
P1+4
15 0
15 0
15 0
15 0
15 0
Offset of linear function
8000 to 7FFF (signed binary)
0001 to 9999 (BCD)
8000 to 7FFF (signed binary)
Maximum conversion
8000 to 7FFF (signed binary)
Minimum conversion
8000 to 7FFF (signed binary)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ - INSTRUCTIONS and is the answer not in the manual?

Omron CJ - INSTRUCTIONS Specifications

General IconGeneral
BrandOmron
ModelCJ - INSTRUCTIONS
CategoryController
LanguageEnglish

Related product manuals