3. Instructions
942
CS/CJ/NSJ Series Instructions Reference Manual (W474)
z Operand Specifications
Flags
Function
When RECV2(492) is executed, the number of receive words specified in C starting with the first source
word specified in S at the source node (i.e., the remote node) in the source network specified in C are
received at the destination node (i.e., the local node). The data is written starting from the word
specified in D at the local node.
When the transmission starts, the Execution Completed Flag in I is turned OFF. When a response is
returned, the transmission results is shown in the Error Flag in I. The communications response is
written to I+1.
The Communications Port Enabled Flags (A202.00 to A202.07) and Communications Port Error Flags
(A219.00 to A219.07) used for the RECV(098) instruction are not used for RECV2(492), which uses the
operand I. The communications port completion code (previously stored in A203 to A210) is stored in
I+1.
Area
Word addresses
Indirect DM/EM
addresses
Con-
stants
Registers Flags
Pulse
bits
TR
bits
CIO WR HR AR T C DM EM
@DM
@EM
*DM
*EM
DR IR
Indirect
using IR
TK CF
S
OK OK OK OK OK OK OK OK OK OK ---
OK
--- OK --- --- --- ---
D
C
---
I
Name Label Operation
Error Flag P_ER • ON if the serial port number specified in C+1 is not between 0 and 4 hex.
• ON if there is no communications port available (i.e., if A211 = 0).
• OFF in all other cases.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ - INSTRUCTIONS and is the answer not in the manual?

Omron CJ - INSTRUCTIONS Specifications

General IconGeneral
BrandOmron
ModelCJ - INSTRUCTIONS
CategoryController
LanguageEnglish

Related product manuals