60
PLC Setup Settings Section 4-2
Pulse Output 0 Origin Proximity Input Signal Type
Pulse Output 0 Limit Input Signal Type
Pulse Output 0 Origin Search/Return Initial Speed
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Pulse Output 0 Origin Search High Speed
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Pulse Output 0 Origin Search Proximity Speed
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Programming
Console setting
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
268 04 to 07 0 hex: NC
1 hex: NO
0 hex Specifies whether the Origin Proxim-
ity Input Signal for pulse output 0 is
normally closed or normally open.
--- When operation
starts
Programming
Console setting
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
268 00 to 03 0 hex: NC
1 hex: NO
0 hex Specifies whether the limit input sig-
nal for pulse output 0 is normally
closed or normally open.
--- When operation
starts
Programming
Console setting
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
258 00 to 15 00000000 to
000186A0 hex
(See note.)
00000000
hex
Specifies the starting speed (0 to
100,000 pps) for the pulse output 0
origin search and origin return opera-
tions.
--- When operation
starts
259 00 to 15
Programming
Console setting
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
260 00 to 15 00000001 to
000186A0 hex
(See note.)
00000000
hex
Specifies the high speed setting (1 to
100,000 pps) for pulse output 0 origin
search operation.
--- When operation
starts
261 00 to 15
Programming
Console setting
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
262 00 to 15 00000001 to
000186A0 hex
(See note.)
00000000
hex
Specifies the proximity speed setting
(1 to 100,000 pps) for pulse output 0
origin search operation.
--- When operation
starts
263 00 to 15

Table of Contents

Other manuals for Omron CJ1M-CPU22

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CJ1M-CPU22 and is the answer not in the manual?

Omron CJ1M-CPU22 Specifications

General IconGeneral
BrandOmron
ModelCJ1M-CPU22
CategoryController
LanguageEnglish

Related product manuals