EasyManuals Logo
Home>Omron>Network Hardware>CS Series

Omron CS Series User Manual

Omron CS Series
290 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #154 background imageLoading...
Page #154 background image
128
Using FINS Applications Section 6-5
6-5 Using FINS Applications
6-5-1 CX-Programmer (CX-Server)
The following examples show how to connect online from a CX-Programmer
on an Ethernet network to a PLC on the Ethernet network.
System Configuration Example 1: No Routing
In this example, an online connection is made by FINS/UDP to a PLC on an
Ethernet network (PLC1 in the diagram below) from a CX-Programmer or CX-
Integrator connected to the Ethernet network.
Conditions
FINS/UDP method
IP address conversion: Automatic generation method (dynamic)
CX-Programmer's Change PLC Dialog Box
CX-Programmer or CX-Integrator
Ethernet (Network address: None)
Ethernet port
Target: PLC1
Ethernet Unit
IP address: 192.168.250.1
FINS/UDP method
Node number: 1
IP address conversion: Automatic
generation method (dynamic)
Ethernet Unit node number: 2
Ethernet Unit IP address: 192.168.250.2
Settings for target PLC (PLC1)'s Change PLC Dialog Box Setting
PLC name PLC1
Network classification Ethernet
Network Tab FINS transmission source address 0
FINS destination Network number 0
Node address 2
Frame length 2,000 bytes
Response monitor time 2 seconds
Driver Tab Workstation node address 1
Automatic generation method Not selected
IP address 192.168.250.2
(Ethernet Unit IP
address)
Port number 9600

Table of Contents

Other manuals for Omron CS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CS Series and is the answer not in the manual?

Omron CS Series Specifications

General IconGeneral
BrandOmron
ModelCS Series
CategoryNetwork Hardware
LanguageEnglish

Related product manuals