55
Converting from Previous Models Section 2-11
Note (1) These limitations do not apply when the CPU Bus Unit System Setup
Area format is in ETN21 mode.
(2) When I/O tables are created using one of the new Ethernet Unit models,
the CPU Bus Unit System Setup Area format is in ETN21 mode from the
beginning.
Checking the CPU Bus Unit System Setup Area Format
Checking with the CX-Programmer's Software Switch Monitor - Status Tab Page
Mail send function • The specifications for previous Units apply.
• The mail transmission status is as follows:
• Status of user mail transmission → Status
of transmission condition setting 5
• Status of periodic mail transmission → Sta-
tus of transmission condition setting 6
• Status of mail transmission when error
occurs → Status of transmission condition
setting 7
Mail receive function • Cannot be used
Automatic clock adjustment function • Cannot be used
DNS server host name • Cannot be used
Item Specifications in ETN11 mode