Com Data
for Modbus
SECTION 6 Communications Data for Modbus
6-18
Status Details
Note 1: When the control output ON time is less than 100 ms, the bit is set to “1” and the heater current is
held at the last current value.
Note 2: “Spare” bits are always OFF.
Note 3: When read in setup area 1, the status of the bits will be as follows:
Bit position Status
Bit Description
0 1
Status
(lower word)
0 Heater overcurrent (CT1) Not generated Generated
1 Heater current hold (CT1) (See note 1.) Update Hold
2 A/D converter error Not generated Generated
3 HS alarm (CT1) OFF ON
4 RSP input error Not generated Generated
5 Display range exceeded Not generated Generated
6 Input error Not generated Generated
7 Potentiometer input error Not generated Generated
8 Control output (heating)/open output OFF ON
9 Control output (cooling)/close output OFF ON
10 HB (heater burnout) alarm (CT1) OFF ON
11 HB (heater burnout) alarm (CT2) OFF ON
12 Alarm 1 OFF ON
13 Alarm 2 OFF ON
14 Alarm 3 OFF ON
15 Program end output OFF ON
Status
(upper word)
16 Event input 1 OFF ON
17 Event input 2 OFF ON
18 Event input 3 OFF ON
19 Event input 4 OFF ON
20 Write mode Backup mode RAM write mode
21 EEPROM RAM = EEPROM RAM
EEPROM
22 Setup area Setup area 0 Setup area 1
23 AT execute/cancel AT canceled AT execution in progress
24 RUN/STOP Run Stop
25 Communications writing OFF (disabled) ON (enabled)
26 Auto/manual switch Automatic mode Manual mode
27 Program start Reset Start
28 Heater overcurrent (CT2) Not generated Generated
29 Heater current hold (CT2) (See note 1.) Update Hold
30 Spare OFF ---
31 HS alarm (CT2) OFF ON
Overcurrent: Last value held Current hold: Last value held
A/D converter error: Last value held Display range exceeded: Last value held
Input error: Last value held RSP input error: Last value held
Potentiometer input error: Last value held Heating output, cooling output, open output,
close output: Cleared
HB and HS outputs: Cleared Alarm outputs: Cleared
Program end output: Cleared

Table of Contents

Other manuals for Omron E5CN-H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN-H and is the answer not in the manual?

Omron E5CN-H Specifications

General IconGeneral
BrandOmron
ModelE5CN-H
CategoryController
LanguageEnglish

Related product manuals