Com Data for
CompoWay/F
SECTION 3 Communications Data for CompoWay/F and SYSWAY
3-20
Status 2 Details
Note 1: “Spare” bits are always OFF.
Note 2: When read in setup area 1, the status of the bits will be as follows:
Overcurrent Output: Cleared
Control Output 1 ON/OFF Count Alarm: Cleared
Control Output 2 ON/OFF Count Alarm: Cleared
Work bits 1 to 8: Cleared
SP ramp: Last value held
Bit position Status
Bit Description
0 1
Status
(lower word)
0 Work bit 1 OFF ON
1 Work bit 2 OFF ON
2 Work bit 3 OFF ON
3 Work bit 4 OFF ON
4 Work bit 5 OFF ON
5 Work bit 6 OFF ON
6 Work bit 7 OFF ON
7 Work bit 8 OFF ON
8 Spare OFF ---
9 Spare OFF ---
10 OC (Heater Overcurrent) Alarm (CT1) OFF ON
11 OC (Heater Overcurrent) Alarm (CT2) OFF ON
12 Control Output 1 ON/OFF Count Alarm Output OFF ON
13 Control Output 2 ON/OFF Count Alarm Output OFF ON
14 Spare OFF
15 Spare OFF ---
Status
(upper word)
16 Spare OFF ---
17 Spare OFF ---
18 Spare OFF ---
19 Spare OFF ---
20 Invert direct/reverse operation Not Invert Invert
21 SP ramp OFF During SP ramp
22 Spare OFF ---
23 Spare OFF ---
24 Spare OFF ---
25 Spare OFF ---
26 Spare OFF ---
27 SP mode Local SP mode Remote SP mode
28 Spare OFF ---
29 Spare OFF ---
30 Spare OFF ---
31 Spare OFF ---

Table of Contents

Other manuals for Omron E5CN-H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN-H and is the answer not in the manual?

Omron E5CN-H Specifications

General IconGeneral
BrandOmron
ModelE5CN-H
CategoryController
LanguageEnglish

Related product manuals