Appendix
Troubleshooting
A-3
Troubleshooting
Before Requesting Repairs
If communications are not functioning properly, check the items in the following table before requesting
repairs. If normal operation cannot be restored even after checking everything, return the product to
your OMRON representative.
Problem: Communications are not possible or communications errors occur.
Item Confirmation Page
The communications wiring is not correct. Correct the wiring. 1-4
The communications line has become
disconnected.
Connect the communications line securely and tighten the
screws.
---
The communications cable is broken. Replace the cable. ---
The communications cable is too long. The total cable length is 500 m maximum for RS-485/RS-422
and 15 m maximum for RS-232C communications. To extend
the communications distance for RS-232C communications,
use OMRONs Z3R Optical Interface.
1-4
1-5
The wrong communications cable has
been used.
Use a shielded, twisted-pair, AWG24 to AWG14 (cross-sec-
tional area of 0.205 to 2.081 mm
2
) cable for the communica-
tions cable.
1-4
1-5
Too many communications devices are
connected to the communications path
for RS-485 communications.
When 1:N, RS-485 communications are used, a maximum of
32 nodes may be connected, including the host node.
1-4
An end node has not been set at each
end of the communications line for RS-
485/RS-422 communications.
Connect or disconnect terminating resistance so that it is
connected only at both ends of the transmission path.
For RS-485 communications, use a terminating resistance of
120 (1/2 W) on the E5CN/AN/EN-H end of the path and
make sure the combined resistance including the terminating
resistance at the host is 54 minimum.
For RS-422 communications, use a terminating resistance of
240 (1/2 W) on the E5AN/EN-H end of the path and make
sure the combined resistance including the terminating resis-
tance at the host is 100 minimum.
1-4
The specified power supply voltage is not
being supplied to the Controller.
Supply the specified power supply voltage. ---
The specified power supply voltage is not
being supplied to an Interface Converter
(e.g., the K3SC).
Supply the specified power supply voltage. ---
The same baud rate and communications
method are not being used by all of the
Controllers, host devices, and other
nodes on the same communications line.
Set the same values for the following on all nodes: baud rate,
protocol, data length, stop bits, and parity.
1-4
The unit number specified in the com-
mand frame is different from the unit
number set for the Controller.
Use the same unit number. 2-2
4-2
5-2
The same unit number as the Controller
is being used for another node on the
same communications line for RS-485/
RS-422 communications.
Set each unit number for only one node. 1-4

Table of Contents

Other manuals for Omron E5CN-H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN-H and is the answer not in the manual?

Omron E5CN-H Specifications

General IconGeneral
BrandOmron
ModelE5CN-H
CategoryController
LanguageEnglish

Related product manuals