CompoWay/F
SECTION 2 CompoWay/F Communications Procedures
2-18
Operation Command
This service performs operations such as the following:
Service Request PDU
Service Response PDU
(1) Command Code and Related Information
Communications
Writing
RUN/STOP Bank Change
AT Execute/Cancel Write Mode Save RAM Data
Software Reset Move to Setup Area 1 Move to Protect Level
Auto/Manual Switch Parameter Initializa-
tion
Alarm Latch Cancel
SP Mode Invert Direct/Reverse
Operation
Program Start
Infrared Communica-
tion Use
Command
code
Command content Related Information
00 Communications Writing 00: OFF (disabled)
01: ON (enabled)
01 RUN/STOP 00: Run
01: Stop
02 Bank Change 00: Bank 0
01: Bank 1
02: Bank 2
03: Bank 3
04: Bank 4
05: Bank 5
06: Bank 6
07: Bank 7
03 AT Execute/Cancel 00: AT cancel
01: 100% AT execute
02: 40% AT execute
04 Write Mode 00: Backup mode
01: RAM write mode
05 Save RAM Data 00
06 Software Reset 00
07 Move to Setup Area 1 00
08 Move to Protect Level 00
MRC SRC
3005
2222
Com-
mand
code
Related
informa-
tion
MRC SRC
3005
22 4
Response
code

Table of Contents

Other manuals for Omron E5CN-H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN-H and is the answer not in the manual?

Omron E5CN-H Specifications

General IconGeneral
BrandOmron
ModelE5CN-H
CategoryController
LanguageEnglish

Related product manuals