Modbus
SECTION 5 Modbus Communications Procedure
5-8
Setup area 0 and setup area 1 do not correspond directly to Modbus
addresses, but the following areas have a rough correspondence with
one exception.
* Partial Exception to Modbus Address Correspondence
The Hysteresis (Heating), Hysteresis (Cooling), Control Period
(Heating), and Control Period (Cooling) parameters are assigned to
consecutive addresses, but the control period parameters are setup
area 1 parameters. For this reason, an operation error will occur when
writing the control period (heating or cooling) from the setup area 0
side, e.g., from the operation level.
Number of Elements The number of elements is expressed in 2-byte hexadecimal. The
setting range for the number of elements varies according to the
command.
For example, when the number of elements is “0010,” this specifies
eight items of data (H’10) from the address.
Four-byte Mode
One element uses 2 bytes of data, so specify two-element units.
Reading and writing in 4-byte units is executed by specifying an even
address and specifying the number of elements in multiples of 2.
Two-byte Mode
One element uses 2 bytes of data, so specify one-element units.
Reading and writing in 2-byte data units is executed by specifying 1-
element units.
Set Values The values read from the variable area or written to the variable area
are expressed in hexadecimal, ignoring the decimal point position.
(Negative values are expressed in 2’s complement format.)
Example: D’105.0 H’0000041A
The variables are 4-digit or 8-digit hexadecimal values. Negative values
are expressed in 2’s complement format. The values are hexadecimal
values with no decimal point indication.
For example, if the E5CN/AN/EN-H's process value is read in 4-byte
mode when the process value is 105.0, the read value will be
H'0000041A (105.0
1050 H'0000041A).
Setup area
Modbus addresses
Area number Address range
Setup area 0 00 to 0B, 20 to 2B 0000 to 0BFE,
2000 to 2B7F
Setup area 1 0C to 15, 2C to 35 0C00 to 15EE,
2C00 to 3577

Table of Contents

Other manuals for Omron E5CN-H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN-H and is the answer not in the manual?

Omron E5CN-H Specifications

General IconGeneral
BrandOmron
ModelE5CN-H
CategoryController
LanguageEnglish

Related product manuals