88
Using Event Inputs Section 4-5
4-5-2 How to Use the Multi-SP Function
The multi-SP function allows you to set up to four set points (SP 0 to 3) in the
adjustment level. The set point can be switched by operating the keys on the
front panel or by using external input signals (event inputs).
Using Event Inputs
â– Two Event Inputs: Event Inputs 1 and 2
The following tables show the relationship between the ON/OFF combinations
of event inputs 1 and 2 and the selected set points.
Number of Multi-SP Uses = 1
Number of Multi-SP Uses = 2
Using Key Operations You can select any of the set points 0 to 3 by changing the set value of the
Multi-SP Uses parameter. The Multi-SP Uses parameter display conditions
are as follows:
• If the Controller does not support event inputs, the Multi-SP Uses param-
eter must be set to ON.
• If the Controller supports event inputs, the Number of Multi-SP Uses
parameter must be set to 0 and the Multi-SP Uses parameter must be set
to ON.
The following table shows the relationship between the Multi-SP Uses param-
eter set value and the selected set point.
Note The set point can also be switched using communications.
4-5-3 Settings
Switching between Set Points 0, 1, 2, and 3
Operating Procedure The following example sets the Number of Multi-SP Uses parameter to 2.
Event input 1 Selected set point
OFF Set point 0
ON Set point 1
Event input 1 Event input 2 Selected set point
OFF OFF Set point 0
ON OFF Set point 1
OFF ON Set point 2
ON ON Set point 3
Multi-SP Selected set point
0Set point 0
1Set point 1
2Set point 2
3Set point 3
Operation Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
C
25
100
PV/SP