Counting Control Output ON/OFF Operations Section 4-20
4-20 Counting Control Output ON/OFF Operations
4-20-1 Control Output ON/OFF Count Function
With Control Output 1 and 2 ON/OFF outputs (relay outputs or voltage outputs
for driving SSR), the number of times that a control output turns ON and OFF
can be counted. Based on the control output ON/OFF count alarm set value,
an alarm can be output and an error can be displayed if the set count value is
exceeded.
The default setting of the Control Output ON/OFF Alarm Setting parameter is
0. ON/OFF operations are not counted when this parameter is set to 0. To
enable counting ON/OFF operations, change the setting to a value other than
0.
Advanced Function Setting Level
3. Press the D Key to enter the password (−169). It is possible to move to
the advanced function setting level by either pressing the M Key or wait-
ing two seconds without pressing any key.
4. Press the M Key to select the PF Setting parameter.
5. Press the U Key to select PFDP (Monitor/Setting Item).
6. Press the M Key to select the Monitor/Setting Item 1 parameter.
7. Press the U Key to select 7 (Alarm Value 1).
Initial Setting Level
8. Press the O Key for at least one second to move from the advanced
function setting level to the initial setting level.
Operation Level
9. Press the O Key for at least one second to move from the initial setting
level to the operation level.
Monitor/Setting Item Level
10. Press the PF Key to display Alarm Value 1.
init
off
Parameter
Initialization
pf
a-m
PF Setting
pf
pfdp
PF Setting
pfd1
1
Monitor/Setting
Item 1
pfd1
7
Monitor/Setting
Item 1
in-t
5
Input Type
C
25
100
al