EasyManuals Logo
Home>Omron>Temperature Controller>E5CN

Omron E5CN User Manual

Omron E5CN
320 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #120 background imageLoading...
Page #120 background image
95
Moving to the Advanced Function Setting Level Section 4-8
4-8 Moving to the Advanced Function Setting Level
To move to the advanced function setting level, you must first cancel the pro-
tection applied by the Initial Setting/Communications Protect parameter.
In the default setting, the advanced function setting level is protected and you
cannot move to this setting level.
1,2,3... 1. Press the O and M Keys simultaneously for at least three seconds in op-
eration level.
Note The key pressing time can be changed in the Move to Protect Level
Time parameter (advanced function setting level).
Protect Level
2. The Controller moves to the protect level, and the Operation/Adjustment
Protect parameter is displayed.
3. Press the M Key once to move to the Initial Setting/Communications Pro-
tect parameter.
4. Set the set value to 0.
Operation Level
5. Press the O and M Keys simultaneously for at least one second to re-
turn to the operation level.
Initial Setting Level
6. Move to the advanced function setting level.
Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
Initial Setting Level
7. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key.
Advanced function setting level
8. Press the D Key, enter the password (−169), and then either press the
M Key or leave the setting for at least two seconds to move to the ad-
vanced function setting level from the initial setting level.
Initial Setting Level
9. To return to the initial setting level, press the O Key for at least one sec-
ond.
Operation Level
10. To return to the operation level, press the O Key for at least one second.
oapt
0
Operation/Adjust-
ment Protect
icpt
1
Initial Setting/
Communica-
tions Protect
icpt
0
C
25
100
PV/SP
in-t
5
Input Type
amov
-169
Move to Ad-
vanced Function
Setting Level
init
off
Parameter
Initialization
in-t
5
Input Type
C
25
100
PV/SP

Table of Contents

Other manuals for Omron E5CN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN and is the answer not in the manual?

Omron E5CN Specifications

General IconGeneral
BrandOmron
ModelE5CN
CategoryTemperature Controller
LanguageEnglish

Related product manuals