116
Using the Simple Program Function Section 4-15
• The program will start when the Program Start parameter is changed from
RSET to STRT. END will be displayed on the No. 2 display and the output
assigned as the program end output will turn ON after the time set in the
Soak Time parameter has expired in the wait band. The Program Pattern
parameter can be used to select moving to STOP mode or continuing
operation in RUN mode after the program ends.
Parameters Related to the Simple Program Function
Note (1) Set for Controllers with Thermocouple/Resistance Thermometer Univer-
sal Inputs. Set “None” as the unit for Controllers with Analog Inputs.
(2) The setting unit of the Wait Band parameter is %FS for Controllers with
Analog Inputs and the setting range is OFF or 0.01 to 99.99.
Program Pattern Either of two program patterns can be selected. The simple program opera-
tion will not be performed if the Program Pattern parameter is set to OFF.
■ Pattern 1 (STOP)
Control will stop and the STOP mode will be entered when the program has
ended.
■ Pattern 2 (CONT)
Control will continue in RUN mode when the program has ended.
Parameter name Symbol Set (monitor) values Unit Display level
Program Pattern ptrn OFF, STOP, CONT --- Initial setting level
Program Start prst RSET, STRT --- Operation level
Soak Time soak 1 to 9999 min or h Adjustment level
Soak Time Unit t-u m (minutes)/h (hours) --- Advanced function set-
ting level
Wait Band wt-b OFF or 0.1 to 999.9 (See note 2.) °C or °F (See notes 1
and 2.)
Adjustment level
Soak Time Remain
Monitor
sktr 0 to 9999 min or h Operation level
RSET → STRT
PV
Set point
Wait band
Wait band
Soak time END display
END output
Automatically switches
from RUN to STOP mode.
RSET → STRT
PV
Set point
Wait band
Wait band
Soak time END display
END output
RUN mode continues.