235
Advanced Function Setting Level Section 5-8
This parameter resets the ON/OFF counter for specified control outputs.
Note After the counter has been reset, the set value will be automatically returned
to 0.
Related Parameters
Control output 1 ON/OFF count monitor, Control output 2 ON/OFF count mon-
itor (advanced function setting level): Page 233
This parameter sets the password to move to the calibration level.
Set the password to move to the calibration level. The password is 1201.
Move to the calibration level either by pressing the M Key or O Key or by
waiting for two seconds to elapse.
Related Parameter
Initial setting/communications protect (protect level): Page 144
rac ON/OFF Counter Reset
Control outputs 1 and 2 must be sup-
ported.
Relay or voltage outputs (for driving
SSR) must be used.
Setting range Default
0: Disable the counter reset function.
1: Reset the control output 1 ON/OFF counter.
2: Reset the control output 2 ON/OFF counter.
0
Function
Setting
See
See
cmov Move to Calibration Level
Initial setting/communications protect
must be 0.
Function
See
See

Table of Contents

Other manuals for Omron E5CN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN and is the answer not in the manual?

Omron E5CN Specifications

General IconGeneral
BrandOmron
ModelE5CN
CategoryTemperature Controller
LanguageEnglish

Related product manuals