45
Setting Output Specifications Section 3-5
Alarms
It will be specified in this section when an alarm must be assigned, i.e., when
an alarm must be set for the Control Output 1 or 2 Assignment parameters, or
for the Auxiliary Output 1 or 3 Assignment parameters. For example, if alarm 1
is set for the Control Output 1 Assignment parameter, then alarm 1 has been
assigned.
Assigning a work bit to either control output 1 or 2 or to auxiliary output 1 to 3
is also considered to be the same as assigning an alarm. For example, if work
bit 1 is set for the Auxiliary Output 1 Assignment parameter, then alarms 1 to 3
have been assigned.
Operating Procedure This procedure sets the following control and auxiliary output assignments.
Control output 1: Control output (heating); Control output 2: Control output
(cooling); Auxiliary output 1: Alarm 1; Auxiliary output 2: Alarm 2
Operation Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
Initial Setting Level
Initial Setting Level
2. Select the Standard or Heating/Cooling parameter by pressing the M
Key.
Initial Setting Level
3. Press the U Key to set the parameter to h-c.
Note The following output assignments do not need to be set because they
are set automatically by changing the control mode, but they are
shown here as a reference for checking the assignments for each out-
put.
4. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key. (For details on moving between levels, refer to 4-8 Moving
to the Advanced Function Setting Level.)
Advanced Function Setting Level
5. Press the D Key to enter the password (“169”), and move from the initial
setting level to the advanced function setting level.
Advanced Function Setting Level
6. Select the Control Output 1 Assignment parameter by pressing the M
Key.
7. Press the U or D Key to set o.
(The default is o.)
C
25
100
PV/S
P
in-t
5
Input Type
5-hc
stnd
Standard or
Heating/Cooling
5-hc
h-c
amov
0
Move to Ad-
vanced Function
Setting Level
init
off
Parameter
Initialization
out1
o
Control Output
1 Assignment
out1
o

Table of Contents

Other manuals for Omron E5CN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN and is the answer not in the manual?

Omron E5CN Specifications

General IconGeneral
BrandOmron
ModelE5CN
CategoryTemperature Controller
LanguageEnglish

Related product manuals