Description of Operation Section 3-2
When STOP is switched to RUN, bumpless processing of the MV output value
does not function (as a result, the startup time required for high-speed tem-
perature-rise control can be shortened).
Note When the calculations are stopped for each function block, alarm processing
and PV input processing also stop. When the RUN/STOP switch is used for
starting and stopping, PID calculations only can be stopped (specified MV is
output) or started.
3-2-11 Monitoring the Run Status of Function Blocks
The run status of function blocks can be monitored as follows:
When monitoring the
run status common to
all function blocks
The run status common to all function blocks on the Loop Controller can be
monitored by one of the following methods.
When monitoring the
run status of
individual function
blocks
The run status of individual function blocks can be monitored by either of the
following methods when the run status common to all function blocks on the
Loop Controller is “running.
3-2-12 Wireless Debugging (LCB01/03/05 Ver. 3.0 or Later)
Wireless debugging refers to the function that performs online debugging of
created function blocks. Wireless debugging uses the following mode.
Calibration Mode This mode enables pseudo-inputs (fixed values) to be forcibly set in the PV
(process value) for the following function blocks.
Function Blocks and ITEMs
Check method Running Stopped
1. RUN LED on front panel of Loop Control-
ler
Lit Out
2. Monitor the run status (Execute - Run -
Monitor run status) on CX-Process Tool
1 (ON): Hot start in progress or
cold start in progress
1 (ON): Stopped
3. ITEM015 of System Common block 0 (OFF) 1 (ON)
ITEM016 of System Common block Hot start: 1 (ON) 0 (OFF)
ITEM017 of System Common block Cold start: 1 (ON) 0 (OFF)
Method Running Stopped
1. Monitor the run status (Monitor run status
- Start) on CX-Process Tool
No indication “Stopped” indicated
2. ITEM000 of each function block 0 (OFF) 1 (ON)
Function block and Block Model ITEM number Settable ITEM Maximum setting Minimum setting
2-position ON/OFF (Block Model
001)
007 PV [PV input value] 115.00 (%) 15.00 (%)
3-position ON/OFF (Block Model
002)
007 PV [PV input value] 115.00 (%) 15.00 (%)
Basic PID (Block Model 011) 007 PV [PV input value] 115.00 (%) 15.00 (%)
Advanced PID (Block Model 012) 007 PV [PV input value] 115.00 (%) 15.00 (%)
Blended PID (Block Model 013) 007 P1 [P1 input value] 9,999 0
Batch Flowrate Capture (Block
Model 014)
007 P1 [P1 input value] 9,999 0
Indication and Setting (Block
Model 031)
007 PV [PV input value] 115.00 (%) 15.00 (%)

Table of Contents

Other manuals for Omron SYSMAC CS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CS Series and is the answer not in the manual?

Omron SYSMAC CS Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CS Series
CategoryController
LanguageEnglish

Related product manuals