144
Exchanging Data with the CPU Unit Section 3-3
3-3-2 Commands from the CPU Unit to the Loop Controller
The Loop Controller's start mode at power ON can be specified from the CPU
Unit.
Auxiliary Area Control Bits Relevant to the Loop Controller
Control Bits (CPU Unit to Loop Controller)
Note When ITEM018 (Start Mode at Power ON) of the System Control block (block
model 000) has been set to “3: Command from CPU Unit,” the Loop Controller
will not operate (including exchanging data with the CPU Unit) until the RDY
LED indicator goes ON and either A60901 or A60902 is set to 1 (ON).
Word Bit Name Explanation Settings Status
when
Run
Mode
Changes
Status
when
power
goes ON
Timing
of
setting
A608 00 Inner Board
Restart Bit
Turn this bit from OFF to ON to restart
the Loop Controller. (The Loop Con-
troller will start initialization.)
Note: The bit will be reset to 0 (OFF)
automatically when initialization is
completed.
0 1: Restarts the
Inner Board
Pre-
served
Cleared User's
choice
A609 01 Start Mode at
Power ON:
Hot Start
(Cannot be
used for Pro-
cess-control
CPU Unit
(CS1D-
CPU@@P).)
When this bit is set to 1 (ON), the
Loop Controller's “start mode at power
ON” will be hot start mode (as a com-
mand from the CPU Unit to the Loop
Controller.)
This bit is effective only when
ITEM018 of the System Control block
(block model 000) is set to 3 (com-
mand from CPU Unit.)
Note: If bits A60901 and A60902 are
both ON at the same time, this bit
takes precedence and a hot start will
be performed.
1: Perform a hot
start when power is
turned ON.
0: If A60902 is also
set to 0, the Board
stops running.
If A60902 is set to 1,
a cold start will be
performed when
power is turned ON.
Pre-
served
Pre-
served
User's
choice
02 Start Mode at
Power ON:
Cold Start
(Cannot be
used for Pro-
cess-control
CPU Unit
(CS1D-
CPU@@P).)
When this bit is set to 1 (ON), the
Loop Controller's “start mode at power
ON” will be cold start mode (as a com-
mand from the CPU Unit to the Loop
Controller.)
This bit is effective only when
ITEM018 of the System Control block
(block model 000) is set to 3 (com-
mand from CPU Unit.)
Note: If bits A60901 and A60902 are
both ON at the same time, A60901
takes precedence and a hot start will
be performed.
1: Perform a cold
start when power is
turned ON.
0: If A60901 is also
set to 0, the Board
stops running.
If A60902 is set to 1,
a hot start will be
performed when
power is turned ON.
Pre-
served
Pre-
served
User's
choice

Table of Contents

Other manuals for Omron SYSMAC CS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CS Series and is the answer not in the manual?

Omron SYSMAC CS Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CS Series
CategoryController
LanguageEnglish

Related product manuals