Bypass-enabled
(Addresses 236, 238)
"Bypass-enabled" zones (keys "on") are zones that can be bypassed during "manual bypass" arming,
"away" arming and auto zone shut-down. The fire zone cannot be bypassed.
Note: If a zone should not be bypassed, turn "off" its corresponding zone key.
System Assignment
(Addresses 240, 242)
Zones selected at these addresses are no longer "common zones", if partitioning is activated. When
partitioning is deactivated, zones selected at these addresses will be armed upon "stay" arming. (See
partitioning, page 26-27, for further explanation.)
Related programming: "Partitioning enabled, address 206, key [8]."
Note: Address 242 should not be programmed for the 718, 728L, and 728 unless the "zone swap"
feature is required.
SYSTEM TIMES
Auto Test report time
ADDRESS
RANGE
244 001 to 255 days, (000 = disabled)
245 000 to 023 hours
246 000 to 059 minutes
Auto arm/report options
1) Report the code programmed at address 175 after the number of days programmed at address 244.
(To disable, program address 244 = 000.)
2) Auto arm the system (on time) if enabled at address 206, key [5].
3) Send a "late to close" code programmed at address 190. (If the system is not armed at this time and
if address 253 ("no movement" time) is disabled by programming the value 000.)
4) If address 253 is not programmed 000, the report codes for "no movement" and "late to close" will be
the same.(Also see "Special timing functions" page 20.)
Exit delay (Address 247)
Range 001 to 255 seconds, (
default 060)
. Applied to all zones upon arming. (000 = disabled)
Entry delay 1 (Address 248)
Range 001 to 255 seconds, (
default 045)
. Applied to all zones not selected at addresses 220 to 234,
upon entry (000 = disabled).
Entry delay 2 (Address 249)
Range 001 to 255 seconds, (
default 045)
. Applied to all zones selected at addresses 232 and 234, upon
entry (000 = disabled).
Bell cut-off time (Address 250)
Range 001 to 255 minutes, (
default 005 minutes)
(000 = disabled).
Normal circuit response time (Address 251)
Range 001 to 255 X 15mSec., (
default 600 mSec)
. Applied to all zones not selected "fast" at addresses
212 and 214. (If selected "fast", circuit response time is 20 mSec) Maximum time 3.8 seconds.
AC report delay (Address 252)
Range 001 to 255 minutes, (
default 030)
(000 = disabled) delay code reported at address 171.
32
IM8

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Paradox Esprit 738 and is the answer not in the manual?

Paradox Esprit 738 Specifications

General IconGeneral
BrandParadox
ModelEsprit 738
CategoryControl Panel
LanguageEnglish

Related product manuals