EV Charge Control Basic
10 / 68
PHOENIX CONTACT 106377_en_04
For further information on the configuration options for the digital inputs and outputs,
please refer to the “Modbus description” on page 53.
3 LO- Locking Control of the locking actuator †
LO+
LD2 Lock Detection Digital input, for connecting the locking confirmation, can be configured †
LD1
PP Proximity Plug Test signal Current carrying capacity of the connected
charging connector and charging cable ac-
cording to
IEC 61851-1
†
CP Control Pilot Pilot wire signal Communication between charging station and
vehicle according to IEC 61851-1, SAE J1772
and GB/T 18487.1
4 SG Signal Ground Ground signal for the RS-485 communication interface
B RS-485 Communication interface
A
5 C2 Contactor Relay output, charging contactor Switches the mains voltage to the vehicle via an
external
charging contactor when status C or D is reached
and
the enabled inputs and registers are active.
C1
*
Not protected against overload
†
Not for EV-CC-AC1-M3-CC-...
Table 2-1 Connections [...]
No. Name Meaning Description