Parameter Descriptions 9-7
Sets the rate of acceleration for all speed increases. See figure 9.1.
Maximum Frequency / Accel Time = Accel Rate
Sets the rate of deceleration for all speed decreases. See figure 9.2.
Maximum Frequency / Decel Time = Decel Rate
Resets all parameter values to factory defaults. After the reset
function is complete, this parameter sets itself back to 0. This
selection causes an F48 Params Defaulted fault.
P039 Accel Time 1
Range: 0.1 to 600.0 sec
Default: 5.0 sec
See also: P038, P040, A051, A052, A067, A070-A073
Figure 9.1 – Accel Time 1 (P039)
P040 Decel Time 1
Range: 0.1 to 600.0 sec
Default: 5.0 sec
See also: P038, P039, A051, A052, A068, A070-A073
Speed
0
Time
[Maximum Freq]
[Accel Time] [Decel Time]
0
Acceleration
De
c
e
lerat
ion
Figure 9.2 – Decel Time 1 (P040)
P041 Reset to Defaults
Range: 0 = Idle State
1 = Reset Defaults
Default: 0 = Idle State
See also: N/A
Speed
0
Time
[Maximum Freq]
[Accel Time] [Decel Time]
0
Acceleration
De
c
e
lerat
ion

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation MD60 and is the answer not in the manual?

Rockwell Automation MD60 Specifications

General IconGeneral
BrandRockwell Automation
ModelMD60
CategoryDC Drives
LanguageEnglish

Related product manuals