Troubleshoot the System Chapter 9
Startup Information
Messages
Startup messages display in a specific sequence on the terminal during
startup and typically display for a few seconds. These messages
indicate the startup sequence of the terminal but do not require that
you perform any action.
Message # Displayed Message Description
37
(1)
Video Initialized Configures and initializes the graphics video system.
30 Watchdog Test Tests the watchdog circuitry to verify system integrity.
1 RAM Test Tests the RAM memory.
31
(1)
Stuck Key Checks the integrity of the function key hardware.
31.5
(1)
Stuck Touch Checks the integrity of the touch screen hardware.
32
(1)
Battery Test Checks the integrity of the battery hardware.
2.5
(1)
Registry Search Locates and loads the most recent, valid registry. Multiple copies of the registry are
maintained. If power is lost during a registry update, a valid registry is available the next
time power is applied to the terminal.
2 Image Search Checks for new OS firmware upgrade on the external CompactFlash card and the serial port.
11
(2)
Downloading Image Downloads a new OS firmware upgrade to internal RAM. Message may remain on screen
for several minutes.
50
(1)
External CF Transfers a new OS firmware upgrade from the external CompactFlash card to the terminal.
Message may display for several minutes.
20
(2)
Transfer Image Programs the OS firmware just downloaded into RAM. Message may remain on screen for
several minutes.
23
(1)
Internal CF Programs the OS firmware just downloaded into the internal flash memory. Message may
display for several minutes.
24 CRC Check Checks the integrity of the OS firmware.
27
(2)
Decompress System Decompresses the compressed OS firmware into RAM.
28 Starting System Launches the operating system (OS).
29 System Check ### Checks internal file system integrity (### is percent progress indicator).
29.1 System Check Disables internal file system integrity check. Contact technical support.
(1)
The status number and message displays only on the 700 to 1500 terminals.
(2)
The status number and message displays only on the 400 and 600 terminals.

Table of Contents

Other manuals for Rockwell Automation PanelView Plus 1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PanelView Plus 1000 and is the answer not in the manual?

Rockwell Automation PanelView Plus 1000 Specifications

General IconGeneral
BrandRockwell Automation
ModelPanelView Plus 1000
CategoryTouch terminals
LanguageEnglish

Related product manuals