PowerFlex Digital DC Drive User Manual - Publication 20P-UM001C-EN-P - July 2008
Programming and Parameters 3-37
APPLICATIONS
PID Control
757 [PID Clamp]
The PID “clamp” allows a smooth tension setting of a controlled
system winder/unwinder when the calculation of the initial diameter
function cannot be used.
When enabling the drive, the dancer is at the lowest point of its full
scale. In this case, with Par 759 [PID Error] at its maximum value,
the motor could accelerate too fast to properly configure the dancer
for its central operating position. By setting the value of Par 757
[PID Clamp] sufficiently low. e.g, = 1000, when the drive starts and
Par 770 [Enable PD] = 1 “Enable”, the value of Par 759 [PID Error]
is limited to 1000 until the signal coming from the dancer (via Par
763 [PID Feedback]) goes above the value in this field. Then, the
value of [PID Clamp] is automatically returned to its maximum
value of 10000. The PID clamp is kept at 10000 until the drive
stops or Par 770 [Enable PD] = 0 “Disabled”.
Default:
Min/Max:
10000
0 / 10000
759,
763,
770
758 [Feed Fwd PID]
Feedback from the transducer position (dancer) or tension.
Default:
Min/Max:
Read Only
–/+10000
759 [PID Error]
Error value input to the PID function (output of the PID Clamp block).
Default:
Min/Max:
Read Only
–/+10000
760 [PID Setpoint 0]
First offset value added to Par 763 [PID Feedback]. This parameter
can be assigned to an analog input, e.g., for the tension setting when
a load cell must be used as feedback.
Default:
Min/Max:
0
–/+10000
763
761 [PID Setpoint 1]
Second offset value added to Par 763 [PID Feedback].
Default:
Min/Max:
0
–/+10000
763
762 [PID Setpoint Sel]
Selects the offset value added to Par 763 [PID Feedback]. This
parameter can be assigned to a digital input.
Default:
Options:
0 =
0 =
1 =
“Setpoint 0”
“Setpoint 0”
“Setpoint 1”
763
763 [PID Feedback]
Analog input feedback value received from the transducer position
(dancer) or tension (load cell).
Default:
Min/Max:
0
–/+10000
772 [PID Output Sign]
Determines whether the output of the PID regulator is bipolar or
positive (clamp of the negative side).
Default:
Options:
1 =
0 =
1 =
“Bipolar”
“Positive”
“Bipolar”
773 [PID Output Scale]
Scale factor for Par 774 [PID Output]. The value of this parameter
depends on to which parameter you want to send the PID regulator
output.
Default:
Min/Max:
1.00
–/+100.00
774
774 [PID Output]
Displays the PID regulator output.
Note: This parameter can be assigned to an analog output in order to
provide a cascaded reference in multi-drive systems.
Default:
Min/Max:
Read Only
–/+10000
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values
Related
A
A
A
A
A
A
A
A
A
A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex series and is the answer not in the manual?

Rockwell Automation PowerFlex series Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex series
CategoryDC Drives
LanguageEnglish

Related product manuals