PowerFlex Digital DC Drive User Manual - Publication 20P-UM001C-EN-P - July 2008
Appendix A
Supplemental Drive Information
Specifications
For information on . . See page . .
Specifications
A-1
IP20 (NEMA UL/Type Open) Watts Loss A-4
Communication Configurations A-5
Drive Power Circuit Protection A-7
Control Power Circuit Protection Fuses A-15
AC Input Line Reactors and AC Input Contactors A-17
DC Output Contactors and Dynamic Brake Resistor Kits A-19
DC Contactor Crimp Lug Kit Specifications A-21
Category Specification
Agency
Certification
According to file E59272 for the series of the approved devices.
The drive is also designed to meet the following specifications:
NFPA 70 - US National Electrical Code
Category Specification
Drive Type Full Wave Regen, 6 Pulse, Regulated Field Supply
Protection Heat Sink Thermistor: Monitored by microprocessor overtemp trip
Drive Overcurrent Trip
Software Overcurrent Trip:
Hardware Overcurrent Trip:
200% of rated current (typical)
220-300% of rated current (dependent on drive rating)
Line transients: Up to 2000 volts peak per IEC 6100-4-5
Control Logic Noise
Immunity:
Showering arc transients up to 1500V peak
Power Ride-Thru: 15 milliseconds at full load
Logic Control Ride-Thru: 0.5 seconds minimum, 2 seconds typical
Ground Fault Trip: Phase-to-ground on drive output
Short Circuit Trip: Phase-to-phase on drive output
Environment
(1)
(1)
PowerFlex DC drives must be installed in a Pollution Degree 2 environment.
Altitude: 1000 m (3300 ft) max. without derating.
De-rate output power by 1.2% for every 100 meters
(328ft) above 1000 meters (3300ft).
Maximum Surrounding Air
Temperature IP20, NEMA
Type Open: 0 to 50 degrees C (32 to 122 degrees F), typical.
Storage Temp. (all const.): –25 to 55 degrees C (–13 to 131 degrees F)
Atmosphere: Important: Drive must
not be installed in an area where
the ambient atmosphere contains volatile or corrosive
gas, vapors or dust. If the drive is not going to be installed
for a period of time, it must be stored in an area where it
will not be exposed to a corrosive atmosphere.
Relative Humidity: Operating: 5 to 85% non-condensing
Storage: 5 - 95% non-condensing
Shock: 15G peak for 11ms duration (±1.0 ms)
Vibration: 0.152 mm (0.006 in.) displacement, 1G peak