EasyManuals Logo
Home>Rockwell Automation>DC Drives>PowerFlex series

Rockwell Automation PowerFlex series User Manual

Rockwell Automation PowerFlex series
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
PowerFlex Digital DC Drive User Manual - Publication 20P-UM001C-EN-P - July 2008
Installation and Wiring 1-9
Line Reactors / Filters
When connecting the drive directly to the main distribution system an AC
line reactor must be used to guard against system disturbance. The type of
line reactor used depends upon the following:
the current absorbed by the AC input
the AC input voltage
the relative short circuit voltage
the AC input frequency
Refer to AC Input Line Reactors and AC Input Contactors on page A-17
for
a list of recommended AC line reactors.
Using Contactors
When using an AC input contactor, the IEC AC1 rating of the contactor
must be equal to the rated thermal (RMS) current value at the mains input of
the drive.
Drive configurations for AC or DC contactors, with or without a dynamic
brake, are as follows (refer to Typical Power Wiring Diagrams on page 1-17
for wiring examples):
When only an AC contactor is used:
Set parameter 1391
[ContactorControl] to 1 “AC Cntctr” (default
value)
(1)
Set one [Relay Out x Sel] parameter and one [Digital Inx Sel]
parameter to “Contactor” (default value for parameters 1392
[Relay
Out 1 Sel] and 140
[Digital In8 Sel])
When only a DC contactor is used:
Set parameter 1391
[ContactorControl] to 3 “DC Cntctr”
(1)
Set one [Relay Out x Sel] parameter and one [Digital Inx Sel] to
“Contactor” (default value for parameters 1392
[Relay Out 1 Sel]
and 140
[Digital In8 Sel])
When an AC contactor and dynamic brake contactor are used:
Set parameter 1391
[ContactorControl] to “AC Cntctr+DB”
(1)
Set one [Relay Out x Sel] parameter (1392 [Relay Out 1 Sel] or 629
[Relay Out 2 Sel]) to “Contactor” and the other relay output to
“ContactorDB”
Set one [Digital Inx Sel] parameter to “Contactor” (default value
for parameter 140
[Digital In8 Sel])
(1)
Par 1391 [ContactorControl] is contained in the “Advanced” parameter configuration group. Refer to How
Parameters are Organized on page 3-3 for more information.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex series and is the answer not in the manual?

Rockwell Automation PowerFlex series Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex series
CategoryDC Drives
LanguageEnglish

Related product manuals