PowerFlex Digital DC Drive User Manual - Publication 20P-UM001C-EN-P - July 2008
3-42 Programming and Parameters
APPLICATIONS
Diameter Calc
1166 [Diam Preset 2]
Third preset starting diameter. The value of this parameter must be
set between the value of Pars 799 [Minimum Diameter] and 1153
[Max Diameter].
Default:
Min/Max:
Units:
1.00
0.00 / 32.00
m
799,
1153
1167 [Diam Preset 3]
Fourth preset starting diameter. The value of this parameter must be
set between the value of Pars 799 [Minimum Diameter] and 1153
[Max Diameter]. This parameter can be assigned to an analog input. If
an analog input is used, +10V corresponds to the value of [Max
Diameter] and the voltage corresponding to the minimum diameter =
10 x ([Minimum Diameter] / [Max Diameter]).
Default:
Min/Max:
Units:
1.00
0.00 / 32.00
m
799,
1153
1168 [Diam Preset Sel]
Selects the starting diameter for the Diameter Calculation function.
0 = Par 1164 [Diam Preset 0]
1 = Par 1165 [Diam Preset 1]
2 = Par 1166 [Diam Preset 2]
3 = Par 1167 [Diam Preset 3]
This parameter can also be set via two digital inputs programmed as
57 “Diam Preset0” and 58 “Diam Preset1”; the selection in this case is
carried out with binary logic.
Default:
Min/Max:
0
0 / 3
1164,
1165,
1166,
1167
1205 [Diam Inc Dec En]
This parameter It is used to improve system stability for winder/
unwinder applications. If this parameter is enabled and if applied to a
winder, the calculated diameter can never decrease; if applied to an
unwinder, the calculated diameter can never increase.
Default:
Options:
1 =
0 =
1 =
“Enabled”
“Disabled”
“Enabled”
1206 [Diam init filter]
Initial filter on the diameter calculation.
Default:
Min/Max:
Units:
100
0 / 5000
ms
1207 [Diam stdy delay]
The amount of time during which the value of Par 1206 [Diam init
filter] is kept active after the value defined in Par 1155 [Line Spd
Thresh] has been overcome.
Default:
Min/Max:
Units:
0
0 / 60000
ms
1155,
1206
Winder Functions
1171 [Variable J Comp]
Torque compensation due to the wound material as a percentage of
the drive rated current.
Default:
Min/Max:
Units:
0.00
0.00 / 199.99
%
1172 [Constant J Comp]
Compensation of the fixed section (motor, reducer, pin) as a
percentage of the drive rated current.
Default:
Min/Max:
Units:
1.00
– / +100.00
%
1173 [Materl Width Pct]
Width of the wound material as a percentage of the maximum width.
Default:
Min/Max:
Units:
100.00
0.00 / 100.00
%
1174 [Static Friction]
Compensation for static friction as a percentage of the drive rated
current.
Default:
Min/Max:
Units:
0.00
0.00 / 199.99
%
1175 [Dynamic Friction]
Compensation for dynamic friction as a percentage of the drive rated
current.
Default:
Min/Max:
Units:
0.00
0.00 / 199.99
%
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values
Related
A
A
A
“Diam Preset1” “Diam Preset0” Selection
0 0 Par 1164 [Diam Preset 0]
0 1 Par 1165 [Diam Preset 1]
1 0 Par 1166 [Diam Preset 2]
1 1 Par 1167 [Diam Preset 3]
A
A
A
A
A
A
A
A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex series and is the answer not in the manual?

Rockwell Automation PowerFlex series Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex series
CategoryDC Drives
LanguageEnglish

Related product manuals