64/327
Building Technologies Basic Documentation LMV5... CC1P7550en
4 Burner control 22.05.2018
4.2.3.2 Repetition counter
With heavy oil Repetition counter value: Heavy oil direct start
Β
Note:
Changes only become active after a reset (power on / reset)
With start release Repetition limit value: Start prevention
Β
Note:
Changes only become active after a reset (power on / reset)
With safety loop Repetition limit value: Safety loop
Β
Note:
Changes only become active after a reset (power on / reset)
Only LMV50:
With no flame at the
end of safety time
Repetition limited value: No flame at the end of first safety time
Setting choices for gas and oil together:
1…3 ⇓ none…2 repetitions
Note!
Changes only become active after a reset (power on / reset)
Caution!
Setting only in accordance with the relevant application
standard.
With loss of flame Repetition limit value: Loss of flame
Β
Note!
Changes only become active after a reset (power on / reset).
Caution!
Setting only in accordance with the relevant application
standard.
Number of repetitions = setting value - 1.
That is:
∂ Value = 1: No repetition
∂ Value = 2: Equals 1 repetition
Caution!
Value 16 represents an unlimited number of repetitions!