PtP coupling and configuration of CP 340
Manual, 04/2011, A5E00369892-03
131
Diagnostics with the CP 340
8
Introduction
The diagnostics functions of the CP 340 enable you to quickly localize any errors which
occur. The following diagnostics options are available:
Diagnosis via the Display Elements of the CP 340
Diagnosis via the STATUS output of the function blocks
Diagnosis via the S7-300 backplane bus
Diagnostics by means of the diagnostic buffer of the CP 340
Display elements (LED)
The display elements show the operating mode or possible error states of the CP 340. The
display elements give you an initial overview of any internal or external errors as well as
interface-specific errors (see Chapter "Diagnosis via the Display
Elements of the CP 340
(Page 133)")
.
STATUS Output of the FBs
The P_SEND, P_RCV and P_PRINT function blocks have a STATUS output for error
diagnostics. Reading the STATUS output of the function blocks gives you information on
errors which have occurred during communication. You can evaluate the STATUS output in
the user program (see Chapter "Diagnostics Messages of the Fun
ction Blocks P
_SEND,
P_RCV and P_PRINT (Page 134)").
The CP 340 also e
nters the diagnostic events at the STATUS output in its diagnostic buffer.
S7-300 backplane bus
The CP 340 can trigger a diagnostics alarm on the CPU assigned to it. CP 340 provides
4 bytes of diagnostics information at the S7-300 backplane bus. This information is analyzed
via the user program (OB 82) or using a programming device to read from the CPU
diagnostic buffer (see Chapter "Diagnostics via the S7-300 backplane bus (Page 142)").
The CP 34
0 also
writes diagnostic events which have triggered a diagnostics interrupt to its
diagnostic buffer.
If a diagnostics alarm event occurs, the SF LED (red) lights up.

Table of Contents

Other manuals for Siemens SIMATIC CP 340

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CP 340 and is the answer not in the manual?

Siemens SIMATIC CP 340 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CP 340
CategoryComputer Hardware
LanguageEnglish

Related product manuals