Configuring and Parameterizing the CP 340
5.5 Identification data
PtP coupling and configuration of CP 340
98 Manual, 04/2011, A5E00369892-03
5.5 Identification data
Definition
Identification data represent information stored on the module and support you in:
Troubleshooting a plant
Verifying your plant configuration
Locating hardware modifications in a plant
This ID data allows the unambiguous identification of modules in online mode. As of order
no. 6ES7 340–1xH02–0AE0, this data is available on the CP 340.
To view the identification data, select PLC > Module Information , or Read Data Record (see
below).
Reading the identification data
Users can access specific ID data by selecting Read Data Record.
The element of the ID data which is assigned to the corresponding index is found under the
associated data record number.
All data records which contain ID data have a length of 64 bytes.
The table below shows the structure of those data records.
Table 5- 2 Data record structure
Content Length (bytes) Coding (hex)
Header information
SZL ID 2 F1 11
Index 2 00 0x
Length of identification data 2 00 38
Number of blocks which contain ID data 2 00 01
Table 5- 3 Identification data
Identification data
Index 2 00 0x
Identification data associated with the relevant
index
54

Table of Contents

Other manuals for Siemens SIMATIC CP 340

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CP 340 and is the answer not in the manual?

Siemens SIMATIC CP 340 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CP 340
CategoryComputer Hardware
LanguageEnglish

Related product manuals