4.4 AUTO START/STOP OPERATION
Auto mode is selected by pressing the button; a LED besides the button will
illuminate to confirm the operation.
Automatic Start Sequence:
1. When “Remote Start” is active, “Start Delay” timer is initiated;
2. When start delay is over, preheat relay energizes (if configured), “preheat delay XX s”
information will be displayed on LCD;
3. After the above delay, the Fuel Relay is energized, and then one second later, the
Start Relay is engaged. The engine is cranked for a pre-set time. If the pump unit fails
to fire during this cranking attempt then the fuel relay and start relay are disengaged
for the pre-set rest period; “crank rest time” begins and wait for the next crank
attempt.
4. Should this start sequence continue beyond the set number of attempts, the start