APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 58 of 62
12.16 VOLVO EDC3
Suitable engine control mode is TAD1240, TAD1241, and TAD1242.
ECU power supply
Set programmable output 1 as
"ECU power"
CAN communication shielding
line(connect with controller’s
terminal only)
Impedance 120Ω connecting
line is recommended.
Impedance 120Ω connecting
line is recommended.
Engine type: Volvo
NOTE: When this engine type is selected, preheating time should be set to at least 3
seconds.
12.17 VOLVO EDC4
Suitable engine types are TD520, TAD520 (optional), TD720, TAD720 (optional),
TAD721, TAD722, and TAD732.
Expanded 30A relay, and
relay offers battery
voltage for terminal14.
Fuse is 16A
Connect to starter coil directly
Connected to negative of battery
CAN communication shielding
line(connect with controller’s
terminal only)
Impedance 120Ω connecting
line is recommended.
Impedance 120Ω connecting
line is recommended.