9 SENSOR SELECT
1) When reselect sensors, the sensor curve will be transferred into the standard value.
For example, if temperature sensor is SGX (120°C resistor type), its sensor curve
is SGX (120°C resistor type); if select the SGD (120°C resistor type), the
temperature sensor curve is SGD curve.
2) When there is difference between standard sensor curves and using sensor, user
can adjust it in “curve type”.
3) When input the sensor curve, X value (resistor) must be input from small to large,
otherwise, mistake occurs.
4) If select sensor type as “None”, sensor curve is not working and LCD does not
display the sensor information.
5) If there is alarm switch only for the select sensor, user must set the sensor as
“None”, otherwise, maybe shutdown or warning occurs.
6) The headmost or backmost values in the vertical coordinates can be set as same
as below,