Control generator to take load or off
load.
Action when genset is starting and
disconnect when crank successful.
Action when genset is starting and
disconnect when stop is completed.
Used for engine which has idles. Close
before starting and open in warming up
delay; Close during stopping idle
process and open when stop is
completed.
Action in warming up delay and be
controlled by GOV in normal running
process.
Action between the period from “stop
idle” to “failed to stop” and be controlled
by GOV in normal running process.
Used for engines with ETS
electromagnet. Close when stop idle is
over and open when pre-set “ETS
delay” is over.
Active 0.1s when controller enter into
stop idle, used for control part of ECU
dropping to idle speed (temporary
reserved).
Suitable for engines which fitted with
ECU; used for control ECU stop.
Suitable for engines which fitted with
ECU; used for control ECU power
supply.
Active 0.1s when controller enter into
warming up delay; used for control part
of ECU raising to normal speed
(temporary reserved).
Close when detects a successful start
signal.
During cranking process, start battery