HRX-OM-W002-A
Chapter 7 Alarm Notification and Troubleshooting
7.3
Troubleshooting HRR Series
7-6
Other Errors
How to check other errors
The causes and remedies for failures that are not indicated by alarm
numbers are shown in Table 7-2
Table 7-2 Causes and remedies for failures without alarm number
Content of
failure
Cause
Remedy
The operation
panel displays
nothing
The power supply switch is not turned on.
Turn on the power supply switch.
Failure of power supply switch
Replace the power supply switch.
No power supply
(The breaker for the power supply is not
turned on.)
Supply the power.
Trip of breaker due to short-circuit and current
leakage
Repair the short-circuit or current leaking
part.
The [RUN] LED
does not light up
even when the
[RUN/STOP]
switch is pressed.
Communication is set.
Check the presence of communication
setting.
Failure of the [RUN] LED
Replace the controller.
Failure of the [RUN/STOP] switch
Replace the controller.

Table of Contents

Other manuals for SMC Networks HRR012-A*-20 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRR012-A*-20 Series and is the answer not in the manual?

SMC Networks HRR012-A*-20 Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRR012-A*-20 Series
CategoryChiller
LanguageEnglish

Related product manuals