Chapter 8 Control, Inspection, Exchange and Cleaning
HRR Series 8.2 Inspection, exchange, cleaning
Check the operation
condition.
・There should be no abnormality with noise,
vibration, smell, or generation of smoke.
・There should be no active alarm signal.
Facility water
(for water-cooled
type)
Check the facility
water condition.
Temperature, flow rate and pressure are within the
specified range.
If the flow rate is decreasing, the Y type strainer
Check clogging and clean the strainer.
Ventilating condition
(for Air-cooled
type)
Check the condition of
the ventilation grille.
・Make sure the ventilation grille is not obstructed.