User Manual 10 Appendix
Maximum Wiring Distance(unit:m)
Number of In
verter
16AWG / 1.31mm
2
17AWG / 1.026mm
2
18 724 586
19 686 555
20 652 528
21 620 502
22 592 480
23 567 459
24 543 440
25 521 422
NOTICE
In case the specification of the cable used is not included in the table above, when
there is only one inverter, ensure that the line impedance of the input node is less than
300Ω; and when there are multiple inverters connected in the daisy chain, ensure that
the impedance is less than 300Ω/number of inverter.