7 iSolarCloud App User Manual
Network Service
Provider
Grid Type
CitiPower & Powercor ≤ 5 kVA for single-phase & 30 kVA for three-phase
> 30 kVA three-phase
United Energy UE-ST-2008.1: 10 kW for single-phase & 30 kW for three-
phase
UE-ST-2008.2: > 30 kVA three-phase
PowerWater Embedded Generation Notice Photovoltaic Systems:2020
SA Power Networks TS129-2019: < 10 kW for single-phase & 30 kW for three-
phase
TS130-2017: > 30 kW & ≤ 200 kW
TS131-2018: > 200 kW
Horizon Power HPC-9DJ-13-0001-2019: ≤ 10 kVA for single-phase & 30 kVA
for three-phase
HPC-9DJ-13-0002-2019: > 30 kVA & ≤1 MVA
westernpower EDM
33612889-2019
AusNet Services Basic Micro Embedded Generation:2020
For compliance with AS/NZS 4777.2:2020, please select from Australia A/B/C. Please contact your
electricity grid operator for which region to use.
step 6 After finishing the settings, tap TUNR ON DEVICE at the upper right corner and the device will be
initialized. The App will send start instructions and the device will start and operate.
step 7 If the inverter is initialized, the App automatically turns to its home page.
- - End
7.5   Home
After login, the home page is as follows:
80

Table of Contents

Other manuals for Sungrow SG110CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG110CX and is the answer not in the manual?

Sungrow SG110CX Specifications

General IconGeneral
BrandSungrow
ModelSG110CX
CategoryInverter
LanguageEnglish

Related product manuals