User Manual 7 iSolarCloud App
In the European region, such as Sweden, Ireland, Hungary, Portugal, Romania, Greece,
Ukraine etc. whose grid code complies with EN50549, select the parameter EN50549_1
(LV grid- connection) or EN50549_2 (MV grid-connection) with proper manual settings.
In the Brazilian region, set the country code as "Brazil". Selecting "Brazil_230" or
"Brazil_240" will cause setting failure.
step 5
When the country is set to Australia, additionally set the applicable network service provider and
then the grid type. Tap Power Company to select the correct power company.
figure 7-5 Initialization Power Company
The image shown here is for reference only. Refer to the actual interface for the supported network
service providers.
table 7-1 Power Company Information
Network Service
Provider
Grid Type
AS/NZS 4777.2:2015 /
AS/NZS 4777.2:2020 Aus
tralia A
/
AS/NZS 4777.2:2020 Aus
tralia B
/
AS/NZS 4777.2:2020 Aus
tralia C
/
ENERGEX & Ergon Ener
gy
• STNW1170: single phase < 10 kVA & three phase < 30 kVA
• STNW1174 :30 kVA
<
PN ≤ 1500 kVA
Endeavour Energy MDI 0043
Ausgrid NS194
Jemena • ≤ 10kVA per phase (or 30 kVA per three phase)
• ELE GU 0014: 30-200kVA
79